Hotels & Real Estate

Resolving room-to-room noise complaints in a 5-star Bangkok hotel

A central Bangkok hotel faced repeated guest complaints about noise between rooms. We measured the real sound insulation of walls and floors, located the leakage paths, and specified fixes with verifiable targets.

The problem

Complaints about neighbour noise and impact noise from above were hurting review scores and occupancy.

Our approach

  • 1Measured airborne (DnT,w) and impact (L'nT,w) sound insulation between sample rooms with Class 1 instruments
  • 2Traced flanking paths via services penetrations, doors and wall junctions
  • 3Specified remedial works (flanking treatment, door seals) with acceptance targets
  • 4Re-measured after works to verify the result

Standards applied

ISO 16283-1ISO 16283-2ISO 717-1ISO 717-2

Key numbers

42 dB → 52 dB

DnT,w before/after

5

Rooms tested

1 since handover

Complaints after works

Outcome

Airborne insulation between the treated rooms went from DnT,w 42 dB to 52 dB, clearing the ≥ 50 dB acceptance target set for the works with 2 dB of margin. Five rooms were measured before and after. One complaint has been logged since handover, against a running pattern of repeat complaints before.